The whole Power Systems formula sheet, to print
98 formulas in 6 topics, each with when to use it. Each is explained in the topic notes.
IAE Academy: Power Systems formula sheet (GATE EE)
Generation, transmission lines, cables, compensation, insulators and distribution
Read the notesHYDRO POWER OUTPUT
, , in m/s, net head in m, overall efficiency; result in W.
LOAD FACTOR AND CAPACITY FACTOR
Both over the same period; each is at most 1.
DEMAND FACTOR AND DIVERSITY FACTOR
Individual maximum demands occur at different times, so their sum is at least the group's maximum demand. A higher diversity factor means less plant capacity is needed to supply the same consumers.
INDUCTANCE PER PHASE OF A TRANSPOSED THREE-PHASE LINE
is the GMD between phases, the GMR of one phase conductor (self GMD). For a three-phase line, . For a bundled phase, is the bundle GMR from the table below.
CAPACITANCE TO NEUTRAL PER PHASE
Transposed line, ground effect neglected; is the same GMD as for inductance. The capacitance uses the actual radius (or the bundle's equivalent radius built with , not ), because it depends on the surface charge, not on internal flux.
SINGLE-PHASE TWO-WIRE LINE (RADIUS R, SPACING D)
The loop inductance is twice the inductance of one conductor. The line-to-line capacitance is half the capacitance of either conductor to neutral, . Valid for .
PROPERTIES OF ABCD CONSTANTS
holds for any passive, linear, bilateral two-port, such as a transmission line. holds in addition when the two-port is symmetrical; the short, nominal-, nominal-T and long-line models are all symmetrical.
PROPAGATION CONSTANT AND CHARACTERISTIC IMPEDANCE
and are the series impedance and shunt admittance per unit length.
VOLTAGE REGULATION
held constant; magnitudes per phase (or line-to-line throughout). Multiply by 100 for per cent. For a short line . Regulation can be negative, for example with a leading-power-factor load. Efficiency is at the same load.
RECEIVING-END POWER FROM ABCD CONSTANTS
, , , . With line-to-line voltages the result is three-phase power; with line-to-neutral voltages it is power per phase. For a lossless short line (, ) it reduces to .
LOSSLESS LINE: SURGE IMPEDANCE AND SIL
, per unit length; is the line-to-line voltage; SIL is the total three-phase power at which the line draws zero net reactive power. At SIL the voltage magnitude is the same all along the line. Below SIL the line produces net vars and the receiving voltage tends to rise; above SIL it absorbs vars and the voltage sags.
FERRANTI EFFECT (LOSSLESS, OPEN RECEIVING END)
The receiving-end voltage exceeds the sending-end voltage because the line charging current flows through the series inductance. The approximation holds for small ; it equals with , per unit length, so the rise grows roughly with the square of the length.
POWER-ANGLE RELATION (LOSSLESS LINE)
is the series reactance of the line; is the angle by which leads . Maximum power at is (steady-state limit). Use line-to-line voltages for three-phase power and line-to-neutral voltages for power per phase. For a long lossless line, replace by .
CAPACITANCE AND INSULATION RESISTANCE OF A SINGLE-CORE CABLE
The insulation resistance is radial, so it is inversely proportional to the cable length .
DIELECTRIC STRESS IN A CABLE
is the voltage between conductor and sheath (use rms for rms stress), . Stress is greatest at the conductor surface and least at the sheath.
THREE-CORE CABLE: CAPACITANCE PER PHASE
is the core-to-sheath and the core-to-core capacitance. : all three cores bunched, measured against the sheath. : two cores bunched with the sheath, measured against the third core. is the capacitance of each core to neutral; the charging current per phase is .
SERIES COMPENSATION
is the degree of series compensation. Then , raised by the factor . Voltage drop and regulation also improve.
REACTIVE POWER OF A SHUNT ELEMENT
A shunt capacitor supplies and a shunt reactor absorbs it. Use and on a consistent basis: per phase with , or three-phase with the line-to-line voltage and star-connected per phase. A capacitor's output falls as , so it gives least support when the voltage is low.
VOLTAGE ACROSS UNITS OF A THREE-UNIT STRING
Units numbered from the cross-arm end; the total string voltage is (phase-to-earth), and is the largest.
STRING EFFICIENCY
It is at most 100%, reached only if , and it falls as increases. Capacitance grading (units of different capacitance), a guard ring (static shielding) and longer cross-arms (smaller ) all improve it.
APPROXIMATE VOLTAGE DROP OF A SECTION (PER PHASE)
Lagging load of power factor and current ; and are the per-phase resistance and reactance of the section. Valid when the angle between the two end voltages is small. A leading load makes the term negative.
UNIFORMLY LOADED DISTRIBUTOR FED AT ONE END
Load current per unit length constant along the whole length, at unity power factor (or DC). is the total load current and the distributor resistance (the loop resistance of both conductors for a two-wire DC or single-phase distributor). The drop is half that of the same total current concentrated at the far end.
UNIFORMLY LOADED DISTRIBUTOR FED AT BOTH ENDS WITH EQUAL VOLTAGES
Same symbols and conditions as above. The minimum voltage is at the mid-point.
Per-unit system, bus admittance matrix and load flow
Read the notesBASE CURRENT AND BASE IMPEDANCE
Three-phase MVA base in MVA and line-to-line kV base in kV; the impedance is per phase of the equivalent star.
PER-UNIT IMPEDANCE
Per-unit voltage, current and power follow in the same way: , , .
CHANGE OF BASE
Used when an equipment rating (given on its own MVA and kV) must be moved to the system base; the rated MVA and kV are the old base.
BASE VOLTAGE ACROSS A TRANSFORMER
Line-to-line rated voltages of the transformer; is unchanged across it.
COMPLEX POWER INJECTED AT BUS $I$
Phasors in per unit; are elements of the bus admittance matrix.
REAL AND REACTIVE POWER EQUATIONS
Here and . The equations are non-linear, so they are solved by iteration.
ELEMENTS OF THE BUS ADMITTANCE MATRIX
is the total shunt admittance from bus to ground; is the series admittance between and . Valid with no mutual coupling and nominal-ratio transformers.
GAUSS-SEIDEL UPDATE (PQ BUS)
and are net injections in per unit. Buses already updated in this iteration use their new values.
NEWTON-RAPHSON CORRECTION EQUATION
Mismatch , ; update , and repeat.
SIZE OF THE JACOBIAN
buses, one slack, PV buses (polar form). is , is , is and is .
DC LOAD FLOW
Assumes pu at all buses, , small angle differences, so . Angles in radians. is the same matrix as in the fast decoupled method (from , slack row and column removed), and holds the net real-power injections of the non-slack buses. It gives real power flows only, and no losses.
Economic dispatch, voltage and frequency control, power factor correction
Read the notesQUADRATIC COST AND INCREMENTAL COST
Cost in Rs/h, in MW; incremental cost is in Rs/MWh and is linear in .
EQUAL INCREMENTAL COST CRITERION (NO LOSSES)
A unit held at has ; a unit held at has . is the system incremental cost in Rs/MWh.
CLOSED FORM FOR QUADRATIC COSTS
Valid while every unit is inside its limits. The fixed term does not affect the dispatch.
B-COEFFICIENT LOSS FORMULA
Symmetric . For two units: . is the incremental transmission loss of unit .
COORDINATION EQUATIONS
Holds for units inside limits. Here is the incremental cost of power delivered at the load.
PENALTY FACTOR FORM
Every unit inside limits has the same product of penalty factor and incremental cost. The approximation holds when is small. A unit with larger has a larger and so a lower optimal IC.
GOVERNOR DROOP
in per unit on the unit's own rating; is the change in generator output in steady state with the speed changer setting fixed.
LOAD SHARING OF PARALLEL UNITS
All units settle at one common frequency. A smaller or a larger rating takes a larger share of a load change, as long as no unit reaches its limit.
STEADY-STATE FREQUENCY CHANGE FOR A LOAD CHANGE
Free governor action, no supplementary control. is the load increase in MW and is load damping in MW/Hz (set if not given).
AREA FREQUENCY RESPONSE CHARACTERISTIC
For one isolated area with governor action only (no integral control). is the governor response of unit and the load damping.
TWO AREAS, GOVERNOR ACTION ONLY
Steady state with no supplementary control; is the change in flow from area 1 to area 2. For a load step in area 1 only, : area 2 sends part of the step over the tie line.
AREA CONTROL ERROR
is the tie-line flow deviation (positive out of the area) and is the frequency bias in MW/Hz, commonly set equal to the area's . The integral controller changes the set point as : negative ACE raises generation.
APPROXIMATE VOLTAGE DROP ON A LINE
Per phase or per unit consistently; and are the real and lagging reactive power received, the receiving-end voltage; valid for a small angle across the line. In a mainly inductive line () the drop depends mostly on .
VOLTAGE RISE FROM REACTIVE INJECTION
Reactive power injected (for example by a shunt capacitor) at a bus whose Thevenin source reactance is ; is the three-phase short-circuit level at that bus (per-unit form, dominant).
OFF-NOMINAL TAP SETTING FOR A LINE
Tap-changing transformers at both ends of a line of impedance . and are the nominal voltages at the two ends referred to the line side, and are the power received at end 2, and the angle across the line is small. With : .
CAPACITOR RATING
Total three-phase kVAr for total real power in kW. The rating is the reactive power the bank delivers at its rated voltage.
CAPACITANCE FROM THE KVAR RATING
is the three-phase VAr, the line voltage in V, , and comes out in F. Note .
EFFECT ON LINE CURRENT AND LOSS
At constant and constant load voltage, the source-side current falls when , and feeder loss falls with its square.
MOST ECONOMICAL POWER FACTOR
Constant ; demand charge per kVA of maximum demand per year and capacitor annual cost per kVAr per year (both linear). It minimises .
Symmetrical components and fault analysis
Read the notesTHE A-OPERATOR
Multiplying a phasor by rotates it by anticlockwise without changing its magnitude. Also .
SYNTHESIS (PHASE FROM SEQUENCE)
Same form for currents. Here and .
ANALYSIS (SEQUENCE FROM PHASE)
Same form for currents. The inverse matrix is times the complex conjugate of the synthesis matrix.
NEUTRAL CURRENT
Only the zero-sequence component flows in the neutral (or earth) return path. If there is no neutral path, in the line currents. So the line currents of a three-wire system (delta or ungrounded star) contain no zero-sequence component, although zero-sequence current can still circulate inside a delta winding.
THREE-PHASE COMPLEX POWER IN SEQUENCE COMPONENTS
The factor 3 appears because the transformation used here (with in the analysis equations) is not power-invariant. There are no cross terms between different sequences.
SEQUENCE NETWORK EQUATIONS AT THE FAULT BUS
For a system that is balanced before the fault, with balanced sources, only the positive-sequence network has a source: , the pre-fault voltage of the reference phase at the fault bus. The negative and zero networks are passive. are the Thevenin impedances seen from the fault point, and are the sequence currents flowing out of the system into the fault.
NEUTRAL IMPEDANCE IN THE ZERO-SEQUENCE NETWORK
A neutral impedance carries , so it appears as in the single-phase zero-sequence network. It does not appear in the positive or negative networks.
THREE-PHASE FAULT CURRENT (PER UNIT)
is the positive-sequence Thevenin impedance at the fault bus, the impedance in each phase of the fault. For a bolted fault .
BASE CURRENT
in VA for the three-phase rating and the line-to-line voltage in volts, giving in amperes.
FAULT MVA (SHORT-CIRCUIT CAPACITY)
For a bolted three-phase fault with pu. In per unit it equals . is in MVA, is the base (rated) line-to-line voltage in volts and is the fault current in amperes.
CHANGE OF BASE
Convert every element to the common MVA base, and to the common voltage base in each voltage zone, before combining.
SHORT CIRCUIT OF A SERIES R-L CIRCUIT (DC OFFSET)
A voltage drives a series - circuit that carries no current at . The angle sets the instant of the fault on the voltage wave. There is no DC offset when . The DC offset is largest when . Then, if is small compared with , the first current peak approaches , twice the steady-state peak. This model takes a constant reactance and ignores the machine's change from sub-transient to synchronous reactance.
SINGLE LINE-TO-GROUND FAULT (PHASE A)
Fault conditions: and . The fault current through the ground is .
LINE-TO-LINE FAULT (PHASES B AND C)
is the impedance connected between and . and . No current flows to ground.
DOUBLE LINE-TO-GROUND FAULT (PHASES B AND C TO GROUND)
is the impedance in the common earth path of both phases. and the current into the ground is .
THREE-PHASE FAULT USING Z_BUS
is the pre-fault voltage at bus , the post-fault voltage at bus , and the positive-sequence matrix.
SEQUENCE VOLTAGES AT BUS I FOR AN UNSYMMETRICAL FAULT AT BUS K
Find the sequence fault currents from the formulas of the previous section with , , and . Each sequence voltage is updated with its own matrix, then combined into phase voltages with the synthesis matrix. If a star-delta transformer lies between buses and , shift the positive and negative sequence values by its phase shift before combining.
ADDING A BRANCH TO EXISTING BUSES (KRON REDUCTION)
Apply to every element of the existing matrix. Both results come from adding a temporary extra row and column and eliminating it.
Protection and circuit breakers
Read the notesRELAY (SECONDARY) QUANTITIES
N_CT = CT ratio and N_VT = VT ratio, each as primary over secondary. Z_pri is the impedance in primary ohms, from the primary voltage and current.
PLUG SETTING MULTIPLIER
Pickup current = plug setting (as a fraction) times the CT rated secondary current. The relay operates only if PSM > 1.
IDMT OPERATING TIME (IEC STANDARD CURVES)
k and alpha depend on the characteristic (table below). Time is in seconds, and the TMS scales the TMS = 1 curve linearly. If a problem gives its own curve, or a table of operating times against PSM for TMS = 1, read the time from it and multiply by the TMS.
PERCENTAGE DIFFERENTIAL RELAY
I_1 and I_2 are the CT secondary current phasors at the two ends, both taken in the same sense through the zone. K is the slope (bias) setting, for example 0.2 for 20 %. A small minimum pickup is usually added.
CT RATIO BALANCE, DELTA-STAR TRANSFORMER
I_L,Delta = line current on the power transformer's delta-winding side, whose CTs are in star. I_L,Y = line current on the star-winding side, whose CTs are in delta. N = ratio of each CT set, primary over secondary. Both sides refer to the same through load.
MHO CHARACTERISTIC
Z_r = relay reach (the diameter) along the maximum-torque angle tau. theta = angle of the measured impedance. The reach shrinks as the impedance angle moves away from tau. j is the imaginary unit.
UNIVERSAL RELAY TORQUE EQUATION
theta = angle by which I lags V, so Z = V/I at angle theta. K_4 (spring restraint) is neglected in the three special cases. Here a negative constant restrains and a positive one operates.
IMPEDANCE SEEN FOR PHASE AND EARTH FAULTS
x = distance to a bolted fault, Z_1 and Z_0 = positive- and zero-sequence line impedance per unit length, phasor quantities measured at the relay. The phase pair (b, c) works for any fault involving those two phases. The earth-fault element on phase a needs the residual compensation k_0, or it measures the wrong distance.
RESTRIKING VOLTAGE (UNDAMPED LC)
Assumes resistance is neglected and the system voltage is constant during the transient (f_n is much higher than the supply frequency). V_m = system voltage across the pole at current zero; for a purely inductive fault circuit this is the peak phase voltage. L and C = inductance and capacitance of the circuit seen from the breaker. The peak occurs at t = pi/omega_n and the maximum RRRV at t = pi/(2 omega_n). The average RRRV up to the peak is 2V_m/(pi/omega_n) = 4 V_m f_n.
CRITICAL DAMPING RESISTANCE
For the source inductance L in series, with a resistor R across the contacts in parallel with the capacitance C. If R <= R_crit, the restriking voltage is non-oscillatory.
BREAKING AND MAKING CAPACITY (THREE-PHASE)
V_L = rated line voltage in kV. I_b = rated symmetrical (rms) breaking current in kA. Breaking capacity is in MVA. The making current is the peak of the first current loop, about 1.8 x sqrt(2) = 2.55 times the symmetrical rms breaking current. If the current at contact separation has a dc component I_dc, the asymmetrical rms breaking current is sqrt(I_b^2 + I_dc^2).
Power system stability and the equal area criterion
Read the notesSWING EQUATION (PER UNIT)
in electrical radians, in seconds, the system frequency in Hz, and in per unit on the same base as ; is the accelerating power. Equivalent form: with .
SWING EQUATION WITH THE ANGLE IN ELECTRICAL DEGREES
Same equation with in electrical degrees (since rad ). Do not mix the two forms.
INERTIA CONSTANT
Unit: seconds (MJ per MVA). In the second form is in kg m, the synchronous mechanical speed in rad/s and in VA. Stored energy is megajoules when is in MVA.
ELECTRICAL AND MECHANICAL ANGLE
is the number of poles. The swing equation above uses the electrical angle.
CHANGE OF BASE
The stored energy in MJ is fixed; only the MVA it is divided by changes.
EQUIVALENT INERTIA OF MACHINES SWINGING TOGETHER
Applies to machines that swing coherently (same and speed), each on its own rating . The stored energies in MJ add.
POWER-ANGLE EQUATION
and are the voltage magnitudes at the two ends, the total series reactance between them; per unit values give in per unit.
INITIAL ANGLE
Of the two angles with this sine, the stable operating point is the one below .
SYNCHRONISING POWER COEFFICIENT
Positive for (stable), zero at , negative beyond. Units: per unit power per electrical radian.
FREQUENCY OF SMALL OSCILLATION
Undamped natural frequency, from linearising the swing equation about with in radians: .
STEADY-STATE STABILITY LIMIT
Reached when load is increased slowly: beyond the coefficient becomes negative and the machine falls out of step.
EQUAL AREA CONDITION
is the maximum swing angle. Valid for the classical model (constant , no damping).
SUDDEN LOAD (OR $P_M$) CHANGE, SAME CURVE
jumps from to with the network unchanged, ; angles in radians where they multiply . Stable only if with .
POWER-CURVE RATIOS DURING AND AFTER A FAULT
With the same and , each curve's peak is , so the during-fault and post-fault peaks are and , where is the transfer reactance between the machine EMF and the infinite bus in each state.
CRITICAL CLEARING ANGLE, ZERO POWER DURING THE FAULT AND UNCHANGED NETWORK AFTER CLEARING
, , so ; in radians. Typical case: three-phase fault at the machine terminals cleared without a line being lost.
CRITICAL CLEARING TIME, ZERO POWER DURING THE FAULT
Valid only when during the fault () and the rotor starts at synchronous speed, so acceleration is constant; angles in radians, in seconds on the same base as . For the swing equation has to be integrated step by step.