Power Systems formula sheet

98 formulas in 6 topics, each with when to use it. Each is explained in the topic notes.

Print the whole sheet

HYDRO POWER OUTPUT

, , in m/s, net head in m, overall efficiency; result in W.

LOAD FACTOR AND CAPACITY FACTOR

Both over the same period; each is at most 1.

BASE CURRENT AND BASE IMPEDANCE

Three-phase MVA base in MVA and line-to-line kV base in kV; the impedance is per phase of the equivalent star.

PER-UNIT IMPEDANCE

Per-unit voltage, current and power follow in the same way: , , .

QUADRATIC COST AND INCREMENTAL COST

Cost in Rs/h, in MW; incremental cost is in Rs/MWh and is linear in .

EQUAL INCREMENTAL COST CRITERION (NO LOSSES)

A unit held at has ; a unit held at has . is the system incremental cost in Rs/MWh.

THE A-OPERATOR

Multiplying a phasor by rotates it by anticlockwise without changing its magnitude. Also .

SYNTHESIS (PHASE FROM SEQUENCE)

Same form for currents. Here and .

RELAY (SECONDARY) QUANTITIES

N_CT = CT ratio and N_VT = VT ratio, each as primary over secondary. Z_pri is the impedance in primary ohms, from the primary voltage and current.

PLUG SETTING MULTIPLIER

Pickup current = plug setting (as a fraction) times the CT rated secondary current. The relay operates only if PSM > 1.

SWING EQUATION (PER UNIT)

in electrical radians, in seconds, the system frequency in Hz, and in per unit on the same base as ; is the accelerating power. Equivalent form: with .

SWING EQUATION WITH THE ANGLE IN ELECTRICAL DEGREES

Same equation with in electrical degrees (since rad ). Do not mix the two forms.