Per unit & load flow formulas
Per-unit system, bus admittance matrix and load flow. 11 formulas for GATE EE Power Systems, each with when to use it. Each is explained in the topic notes.
IAE Academy: Per-unit system, bus admittance matrix and load flow formulas (GATE EE)
All 11 Per unit & load flow formulas
BASE CURRENT AND BASE IMPEDANCE
Three-phase MVA base in MVA and line-to-line kV base in kV; the impedance is per phase of the equivalent star.
PER-UNIT IMPEDANCE
Per-unit voltage, current and power follow in the same way: , , .
CHANGE OF BASE
Used when an equipment rating (given on its own MVA and kV) must be moved to the system base; the rated MVA and kV are the old base.
BASE VOLTAGE ACROSS A TRANSFORMER
Line-to-line rated voltages of the transformer; is unchanged across it.
COMPLEX POWER INJECTED AT BUS $I$
Phasors in per unit; are elements of the bus admittance matrix.
REAL AND REACTIVE POWER EQUATIONS
Here and . The equations are non-linear, so they are solved by iteration.
ELEMENTS OF THE BUS ADMITTANCE MATRIX
is the total shunt admittance from bus to ground; is the series admittance between and . Valid with no mutual coupling and nominal-ratio transformers.
GAUSS-SEIDEL UPDATE (PQ BUS)
and are net injections in per unit. Buses already updated in this iteration use their new values.
NEWTON-RAPHSON CORRECTION EQUATION
Mismatch , ; update , and repeat.
SIZE OF THE JACOBIAN
buses, one slack, PV buses (polar form). is , is , is and is .
DC LOAD FLOW
Assumes pu at all buses, , small angle differences, so . Angles in radians. is the same matrix as in the fast decoupled method (from , slack row and column removed), and holds the net real-power injections of the non-slack buses. It gives real power flows only, and no losses.