The whole Networks (Electric Circuits) formula sheet, to print
166 formulas in 7 topics, each with when to use it. Each is explained in the topic notes.
IAE Academy: Networks (Electric Circuits) formula sheet (GATE EC, EE, IN)
Circuit laws, sources, and node and mesh analysis
Read the notesRESISTOR (OHM'S LAW)
Linear resistor, passive sign convention. Conductance (siemens), so .
INDUCTOR
Passive sign convention. The stored energy depends only on the present current. In DC steady state , so an inductor behaves as a short circuit.
CAPACITOR
Passive sign convention. In DC steady state , so a capacitor behaves as an open circuit.
CONTINUITY OF CAPACITOR VOLTAGE AND INDUCTOR CURRENT
is the instant just before the switching and the instant just after. The rule holds whenever the capacitor current and the inductor voltage stay finite (no impulses). That is guaranteed when the sources are finite and the switching creates no loop made only of capacitors and ideal voltage sources and no cut-set made only of inductors and ideal current sources. If such a loop is formed, the capacitor voltages are forced to jump (solve with charge conservation); if such a cut-set is formed, the inductor currents are forced to jump (solve with flux-linkage conservation). Capacitor current, inductor voltage and resistor quantities CAN jump at .
SERIES AND PARALLEL COMBINATIONS
Inductors without mutual coupling. Two resistors in parallel give , and two capacitors in series give . Series capacitors that start uncharged carry equal charge.
COUPLED INDUCTORS (DOT CONVENTION)
Each coil uses the passive sign convention for its own and . Take +M when both currents enter (or both leave) the dotted terminals, and −M when one enters a dot and the other leaves one. means perfect coupling.
COUPLED INDUCTORS IN SERIES AND PARALLEL; STORED ENERGY
For : upper sign = aiding (in series, the current enters both dotted terminals in turn; in parallel, the dotted terminals are joined together), lower sign = opposing. For the energy: when and both enter (or both leave) the dotted terminals, otherwise. for all currents, which is why .
COUPLED COILS WITH A COMMON TERMINAL (T-EQUIVALENT)
Two coupled coils that share one terminal can be replaced by an uncoupled T network: series arm on coil 1's side, series arm on coil 2's side, and shunt arm to the common terminal. "Like terminals joined" means both dotted ends (or both undotted ends) meet at the common terminal. A negative inductance in the model is only a mathematical element; the behaviour at the three terminals is exact.
CHARGE SHARING BETWEEN TWO CAPACITORS
Capacitors charged to and are connected in parallel, + plate to + plate. If they are joined with opposite polarities, replace by . The total charge is conserved; the energy is dissipated in the connecting resistance, whatever its value.
SOURCE TRANSFORMATION
in series with is equivalent at its two terminals to in parallel with the same . The current-source arrow points toward the terminal that was + on the voltage source. The two are equivalent only at the terminals: the power dissipated inside differs. An ideal source (no ) cannot be transformed. A dependent source can be transformed the same way, provided its controlling variable is not the current or voltage of the resistor being transformed, because that quantity changes in the transformation.
KIRCHHOFF'S CURRENT LAW
Equivalently, total current entering = total current leaving. It also holds for a closed surface enclosing several nodes, which is the basis of the supernode.
KIRCHHOFF'S VOLTAGE LAW
Count a drop as positive when the loop crosses an element from + to −. It holds for any closed path, including one through a current source or across an open gap (the voltage there is then an unknown).
VOLTAGE DIVISION
Resistors in series carrying the same current, with nothing else drawing current from the tap. For impedances, replace by .
CURRENT DIVISION
Branches in parallel across the same voltage. With two branches, the current in one is proportional to the OTHER branch's resistance.
BALANCED WHEATSTONE BRIDGE
A bridge with arms A–C–B and A–D–B and an element between C and D. When the bridge is balanced and the C–D element contains no source, that element carries no current and can be removed or replaced by a short without changing anything else.
CUBE OF TWELVE EQUAL RESISTORS
Resistance between two corners of a cube whose twelve edges are each : opposite corners of the cube, opposite corners of one face, and the two ends of one edge. Each follows from symmetry: join the corners that are at equal potential, then reduce.
INFINITE LADDER NETWORK
A ladder that starts at the input with a series resistor , then a shunt resistor , repeated without end. Adding one more section does not change the input resistance, so , and the formula is the positive root. If the ladder starts with the shunt arm instead, its input resistance is with from the formula.
DELTA TO STAR
Star arm at a node = product of the two delta resistors touching that node ÷ sum of all three delta resistors.
STAR TO DELTA
Delta resistor between two nodes = sum of the pairwise products of the star arms ÷ the star arm at the OPPOSITE (third) node. Equivalently, .
BALANCED (EQUAL-ARM) CASE
All three arms equal. The same relation holds for equal impedances at a single frequency, for example a balanced three-phase load.
NODAL EQUATIONS BY INSPECTION
Valid for circuits with only resistors and independent current sources. = net source current injected INTO node . The matrix is symmetric; a dependent source breaks the symmetry and has to be added by hand.
MESH EQUATIONS BY INSPECTION
Valid when all mesh currents are clockwise and the circuit has only resistors and independent voltage sources. = algebraic sum of the source voltages driving current in mesh 's direction (rises positive). The matrix is symmetric unless dependent sources are present.
NUMBER OF KCL OR KVL EQUATIONS TO WRITE
= nodes and = branches of a connected circuit, counting every element as a separate branch. = voltage sources (independent or dependent); each fixes a node voltage or supplies a supernode constraint, so one KCL equation fewer is needed. = current sources (independent or dependent); each fixes a mesh current or supplies a supermesh constraint. A dependent source's constraint is still expressed in the unknowns, so it has to be substituted, not just read off. Assumes no loop made only of voltage sources and no cut-set made only of current sources. Choose the method that needs fewer equations.
POWER, ENERGY AND POWER BALANCE
Passive sign convention. J.
SAFE CURRENT AND VOLTAGE OF A RATED RESISTOR
The power rating is the largest power a component can dissipate continuously without overheating. In series, the smallest limits the whole string; in parallel, the smallest limits.
EFFICIENCY
Losses are the power dissipated in resistances, for example in conductors and in a source's internal resistance.
PRACTICAL SOURCE FEEDING A RESISTIVE LOAD
is the fraction of the power generated by the ideal part, , that reaches . It approaches 100% as .
MAXIMUM POWER FROM A PRACTICAL SOURCE
Fixed and with a variable resistive load. Maximum power transfer and maximum efficiency happen at different operating points. If instead is fixed and can be chosen, is largest at , not at : the matching condition applies only when the load is the variable.
BATTERY WITH INTERNAL RESISTANCE
= EMF (the open-circuit voltage, which depends on the state of charge), = internal resistance, = magnitude of the current. Short-circuit current is . Stored energy ≈ nominal voltage × capacity in Ah, which gives Wh.
SOLAR CELL (IDEAL SINGLE-DIODE MODEL)
Generator convention: is the current delivered out of the + terminal. is the photocurrent (proportional to irradiance), the diode saturation current, the ideality factor, and mV at 300 K. Series and shunt resistances are neglected.
TWIGS AND LINKS OF A CONNECTED GRAPH
For a graph with separate parts: twigs and links .
INDEPENDENT EQUATIONS
Connected graph. For a planar graph, is also the number of meshes (windows).
Network theorems
Read the notesPOWER AND RMS VALUE WITH COMPONENTS AT DIFFERENT FREQUENCIES
= DC component; = rms value of the component at frequency , with all the non-zero and distinct. Here average powers do add, because the cross terms average to zero over time. Two components at the same frequency do not: combine them as phasors first. Example: A gives A.
THEVENIN–NORTON RELATIONS
with a–b open; flows from a to b through a short across a–b. The ratio cannot be used when both are zero. That is always the case for a network with no independent source, and it can also happen when the sources inside produce nothing at a–b (a balanced bridge, for example). Then use the test-source method.
SOURCE TRANSFORMATION
The arrow of points towards the terminal on the side of . The two forms are equivalent only as seen from the terminals: the current and power inside differ. A dependent source can be transformed the same way, provided its controlling variable is not inside the being moved. An ideal voltage source () or an ideal current source () cannot be transformed.
TEST-SOURCE METHOD
Short the independent voltage sources, open the independent current sources, and leave every dependent source active. Apply across a–b ( at a) and find the current entering terminal a from the test source (or inject into a and find ). This works whenever the equivalent exists, and it is the method to use when the network has no independent source.
MAXIMUM POWER TRANSFER, RESISTIVE LOAD
is fixed and varies. If the network has dependent sources, use the found with them active.
LOAD POWER FOR ANY LOAD RESISTANCE
rises for and falls for . So if is restricted to a range that excludes , the best choice is the allowed value nearest .
EFFICIENCY OF THE THEVENIN EQUIVALENT
This is the efficiency of the Thevenin equivalent circuit only. The power drawn from the sources inside the original network is different, so the real efficiency at matching is generally not 50%.
AC MAXIMUM POWER TRANSFER, CONJUGATE MATCH
Use this when both and are free (and ). The reactances cancel, so the loop is resonant. is an rms value; if the phasor is a peak value , then .
AC SOURCE, PURELY RESISTIVE LOAD
Use this when the load must be a pure resistor (). Choosing here is a common error.
FIXED LOAD REACTANCE, VARIABLE LOAD RESISTANCE
is fixed and varies; is evaluated at that . The pure-resistor case is , which gives back .
FIXED LOAD ANGLE, VARIABLE MAGNITUDE
Use this for a load whose angle is fixed (a fixed power factor) and whose magnitude alone varies; is the angle of . Setting gives back the pure-resistor result, and gives back the conjugate match.
RECIPROCITY CONDITIONS FOR A TWO-PORT
Convention: and both flow INTO their ports, and ABCD is defined by , . Where the parameter sets exist, any one condition implies the others. Symmetry (, ) is a separate, stronger property.
TELLEGEN'S THEOREM
The sums run over all branches. The first form is conservation of power: the power delivered by the sources equals the power absorbed by everything else. The second form pairs voltages from one network with currents from another that has the same graph and the same reference directions. It also holds for one network at two different instants.
MILLMAN'S THEOREM
= ideal current sources between the two nodes, directed into a; they add nothing to the denominator. A passive branch enters with . An ideal voltage source with cannot be included, because it fixes directly.
MILLER'S THEOREM
is removed and replaced by from node 1 to ground and from node 2 to ground. must be the gain with connected. For , is negative; for (a follower), is negative.
MILLER CAPACITANCE
This is the capacitor version (impedance ). For an inverting stage, with . Then is large (the Miller effect), and when . A bridging resistor becomes at the input.
COMPENSATION THEOREM
= original branch current. = impedance seen by the branch looking into the rest of the network, with independent sources off. The minus sign says that increasing the impedance reduces the branch current. A typical use is the error caused by inserting an ammeter of resistance .
Transients in RL, RC and RLC circuits
Read the notesCONTINUITY OF THE STATE VARIABLES
Holds whenever and contain no impulse. It can fail in two ways: a source that itself contains an impulse (such as ), or a switching that creates a loop of capacitors and ideal voltage sources whose voltages do not already satisfy KVL, or a cut-set of inductors and ideal current sources whose currents do not already satisfy KCL (see the tip below). Put in terms of charge and flux linkage: and are continuous.
FIRST DERIVATIVES AT 0+
Find and from the circuit, using KCL and KVL with capacitors replaced by voltage sources and inductors by current sources. A second-order circuit needs this as its second initial condition. For the derivative of a resistor quantity, differentiate its KVL or KCL equation and substitute these values.
TIME CONSTANT
is the resistance seen from the capacitor or inductor terminals with independent voltage sources shorted and independent current sources opened. Keep dependent sources and find with a test source, . Use the circuit that exists after the switching.
COMPLETE RESPONSE OF A FIRST-ORDER CIRCUIT WITH DC SOURCES
Valid for any voltage or current in a first-order circuit with constant sources. is the switching instant (usually ). Use the value, not the value, for anything other than and .
SERIES RC ON A DC SOURCE
DC source switched on at with . flows from the source into the + terminal of the capacitor. gives charging, ; gives discharge, .
SERIES RL ON A DC SOURCE
DC source switched on at with . gives build-up, ; gives decay, . jumps to at ; if the inductor was in DC steady state before switching, .
INITIAL SLOPE AND TIME TO REACH A VALUE
The tangent at the start reaches the final value after exactly one time constant. The second form gives the instant at which reaches a stated value between and .
RISE TIME AND HALF-CHANGE TIME
For a first-order step response. The rise time is the time to go from 10 to 90 percent of the change; is the time for half the change.
SERIES RLC: CHARACTERISTIC EQUATION
For the source-free series loop (a voltage source is replaced by a short). is the damping coefficient (neper frequency, in s) and is the undamped natural frequency (rad/s).
PARALLEL RLC: CHARACTERISTIC EQUATION
For the source-free parallel circuit (a current source is replaced by an open). It has the same as the series case but a different : here a larger means less damping.
ROOTS, DAMPING RATIO AND DAMPED FREQUENCY
Both cases have the form . is real only when . The roots multiply to and add to .
CRITICAL RESISTANCE
A series RLC is overdamped for and underdamped for . A parallel RLC is the other way round: overdamped for , underdamped for .
SERIES RLC SWITCHED ONTO A DC SOURCE: THE CURRENT
DC source applied at , with and ; flows from the source into the + terminal of . All three cases follow from and . With : .
SERIES RLC SWITCHED ONTO A DC SOURCE: THE CAPACITOR VOLTAGE
Same conditions as the current formulas above. Each form satisfies and , and gives back the matching current. With : .
UNDERDAMPED CAPACITOR VOLTAGE: FIRST PEAK AND OVERSHOOT
Same conditions, with , so the first extremum is the maximum (for the same instant gives the lowest point, below ). The extrema of fall at (), the instants where . Successive maxima are one damped period apart, and the overshoot above shrinks by the factor from one maximum to the next. The fractional overshoot is the peak-overshoot formula of the standard second-order system.
LC CIRCUIT (UNDAMPED OSCILLATION)
A capacitor charged to is connected across an uncharged inductor at ; is the current leaving the + terminal of and entering . The energy swings between and every quarter period. An uncharged LC switched onto a DC source gives , which peaks at .
INDUCTOR WITH INITIAL CURRENT
Series model: impedance in series with a voltage source that drives current in the direction of (its + terminal is on the side where leaves). Parallel model: impedance in parallel with a current source pointing in the direction of .
CAPACITOR WITH INITIAL VOLTAGE
Series model: impedance in series with a voltage source of the same polarity as . Parallel model: impedance in parallel with a current source whose arrow points toward the + terminal of (the charged capacitor pushes current out of its + terminal).
INITIAL- AND FINAL-VALUE THEOREMS
For a rational , the initial-value theorem needs to be strictly proper; otherwise has an impulse at . The final-value theorem is valid only when every pole of lies in the open left half-plane. It gives a wrong answer for a sinusoid or a growing response.
NETWORK FUNCTION, IMPULSE RESPONSE AND STEP RESPONSE
Impulse and step responses are defined with every initial condition zero. The zero-state response to any input is , the convolution of with the input. The complete response adds the zero-input response produced by the initial-condition sources. Every pole of is a natural frequency of the circuit; a natural frequency can be missing from a particular when it cancels against a zero, but it still appears in the zero-input response.
DELAYED INPUTS AND RECTANGULAR PULSES
Time-shift property, with . A pulse of height and width applied at zero initial state gives, by linearity and time invariance, the step response minus a copy delayed by (each copy is zero before its own step). For the series RC with output : for , and for .
IMPULSES CHANGE THE STATE INSTANTLY
A current impulse into a capacitor raises its voltage by . A voltage impulse across an inductor raises its current by . When the impulse is the only source, the circuit is source-free after , so the impulse response is the zero-input response from these new initial values.
FIRST-ORDER CIRCUIT WITH ANY SOURCE
is the steady-state response (from phasors, for a sinusoid). This generalises the DC formula, where . The transient term vanishes when .
SERIES RL SWITCHED ONTO A SINUSOID
With . The steady-state current lags the voltage by . The exponential (DC offset) term starts at .
SERIES RC SWITCHED ONTO A SINUSOID
With . The steady-state current leads the voltage by . The current's own transient term is , which gives .
SWITCHING ANGLE FOR NO TRANSIENT
Both come from one rule: there is no transient when the steady-state value of the state variable ( or ) at the switching instant equals its actual initial value, which is zero here. For RL, switch when the steady-state current passes through zero; for RC, switch when the steady-state capacitor voltage does.
WORST-CASE SWITCHING FOR RL
The transient is largest when the switch closes at a peak of the steady-state current. About half a cycle later, the total current's first peak approaches twice the steady-state amplitude, provided the time constant is long compared with the period.
STORED ENERGY
These depend only on the present or , which is why those two quantities are the continuous ones.
CHARGING A CAPACITOR FROM A DC SOURCE THROUGH A RESISTOR
From to the final value , through a resistor of any value. Starting uncharged, the source delivers and exactly half of it is dissipated. If the capacitor discharges toward , and the same holds.
ENERGY DISSIPATED IN AN EXPONENTIAL DECAY
The power decays with time constant . For an RL decay () the total is , and for an RC discharge from it is . After one time constant, of the stored energy has been dissipated.
CHARGE SHARING BETWEEN TWO CAPACITORS
For at and at connected in parallel, through a switch or a resistor. and are measured across the same pair of joined terminals, so a capacitor connected with reversed polarity enters with a negative voltage. The loss does not depend on the connecting resistance , which only sets the time constant .
Sinusoidal steady state, AC power and resonance
Read the notesAVERAGE VALUE
Any periodic waveform; integrate over any one full period.
RMS VALUE
Any periodic waveform. Square first, then average, then take the root.
SINUSOID
. The full-cycle average is zero; the rms value does not depend on the phase .
FORM FACTOR AND CREST (PEAK) FACTOR
is the half-cycle average for a waveform whose full-cycle average is zero; is the largest absolute value. For a sine, and .
RMS OF A SUM OF DIFFERENT FREQUENCIES
Only when the components have different frequencies (dc counts as frequency zero): products of different frequencies average to zero over the common period. Add same-frequency terms as phasors first.
ELEMENT IMPEDANCES
Inductor: voltage leads current by . Capacitor: current leads voltage by . Resistor: in phase.
IMPEDANCE
: inductive, current lags. : capacitive, current leads. is the angle by which voltage leads current. The arctangent form assumes (a passive impedance); for , or with the sign of .
ADMITTANCE
only when . Susceptances: capacitor , inductor .
COMBINATIONS AND DIVIDERS
Same as dc, with complex numbers: the voltage divider is for elements in series, the current divider for two parallel branches. Magnitudes add only when the phasors are in phase.
ACTIVE, REACTIVE AND APPARENT POWER
rms values. is the average of . is the amplitude of the part of that flows back and forth between the source and the fields of L and C, with zero average.
COMPLEX POWER
rms phasors, power absorbed by the load. With peak phasors, . The conjugate goes on the current; writing instead flips the sign of .
POWER IN EACH ELEMENT
and are positive magnitudes. An inductor absorbs reactive power, a capacitor delivers it, and neither absorbs average power.
POWER FACTOR
Lagging when current lags voltage (, , inductive); leading when current leads (, , capacitive); unity at . Always state lagging or leading with the number.
CONSERVATION OF COMPLEX POWER
Every element taken with the passive sign convention. and of loads add whether they are in series or parallel; apparent powers do NOT add in general (only when every load has the same power-factor angle).
SHUNT CAPACITOR FOR PF CORRECTION
, = pf angles before and after (lagging taken positive), = rms voltage across the capacitor, in W. For a final leading pf take negative.
AVERAGE POWER WITH HARMONICS
, = rms values of the -th harmonic; = angle by which leads . A harmonic present in only one of , contributes nothing. Power factor using the full rms values. If is a pure sinusoid and only is distorted, this becomes : distortion factor times displacement factor.
LOAD POWER
rms. Start every restricted-load problem from this expression.
CONJUGATE MATCH
rms (with a peak value it is ). The Thevenin source then delivers twice this power, so the efficiency measured against the Thevenin equivalent is 50%.
PURELY RESISTIVE LOAD
When the load cannot have reactance. Gives less power than the conjugate match unless .
RESONANT FREQUENCY
Ideal series RLC and ideal parallel RLC (frequency-independent R). The value of R does not shift it.
QUALITY FACTOR, SERIES RLC
is the total series resistance, including the coil's own resistance and the source's internal resistance.
VOLTAGE MAGNIFICATION (SERIES)
The L and C voltages are apart and cancel, but each is times the supply voltage.
HALF-POWER FREQUENCIES (SERIES)
Constant-amplitude voltage source. At and : , , , impedance angle at (capacitive) and at (inductive). is their exact geometric mean.
BANDWIDTH (SERIES)
Exact for any . For high (roughly ), ; the arithmetic symmetry about is only approximate, the geometric one is exact.
QUALITY FACTOR AND BANDWIDTH, PARALLEL RLC
Ideal parallel RLC. Current magnification: at , . A current source with internal resistance puts in parallel with : use in and BW.
SERIES-PARALLEL EQUIVALENT AT ONE FREQUENCY
A series and a parallel combination of and have the same impedance at the frequency where the values are computed, and only there. For , and , which is where the tank result below comes from.
PRACTICAL TANK (COIL R, L IN PARALLEL WITH C)
= frequency of unity pf; = dynamic impedance (purely resistive) at that frequency. A real exists only if . Exactly, with the coil taken at this ; for , and .
FIRST-ORDER LOW-PASS
At : ( dB), phase . Asymptotic roll-off dB/decade above .
FIRST-ORDER HIGH-PASS
At : , phase . Asymptotic slope dB/decade below .
STANDARD SECOND-ORDER FORMS
Match the denominator to read and directly: series RLC has , parallel RLC has . Damping ratio . The band-pass and band-stop bandwidth is . Asymptotic slopes: low-pass dB/decade above , high-pass dB/decade below it, band-pass dB/decade on its two skirts.
Magnetically coupled circuits
Read the notesTERMINAL EQUATIONS OF TWO COUPLED COILS (TIME DOMAIN)
Each coil's voltage follows the passive sign convention for that coil (+ at the terminal where its own current enters). Use when both currents enter (or both leave) their dotted terminals and when one enters and the other leaves.
PHASOR (SINUSOIDAL STEADY-STATE) FORM
Same sign rule as the time-domain equations. is the mutual reactance in ohms.
COUPLING COEFFICIENT
: no coupling; : perfect coupling (all the flux of each coil links the other). Coils wound on a common iron core are typically tightly coupled ( close to 1); air-cored coils are usually more loosely coupled.
SERIES CONNECTION
for series-aiding (the junction joins an undotted terminal to a dotted one); for series-opposing (dotted to dotted, or undotted to undotted). Both values are non-negative because .
THREE COUPLED COILS IN SERIES
The same current flows through all three coils. Decide each pair separately with that pair's own marks: if the current enters both of the pair's marked terminals (or leaves both), otherwise.
MUTUAL INDUCTANCE FROM TWO SERIES MEASUREMENTS
Measure the series pair, reverse one coil and measure again. The larger reading is always the aiding one.
PARALLEL CONNECTION
in the denominator when like terminals are joined (both dots on the same node: parallel-aiding); when unlike terminals are joined (parallel-opposing). Coil resistances neglected. With the numerator is zero, so , except for two equal coils () in parallel-aiding, where the formula reads and .
ENERGY STORED IN TWO COUPLED COILS
Instantaneous currents. when both currents enter (or both leave) their dotted terminals, otherwise: the same rule as for the voltages.
T-EQUIVALENT OF COUPLED COILS
and are the series arms on the coil-1 and coil-2 sides, the shunt arm to the common terminal. Valid only when the two coils share a common terminal (or their lower terminals are joined in the circuit), because the T adds that connection. "Same side" means both dots away from the common terminal or both on it. A negative inductance in the model is acceptable for analysis, although it is not a physical element.
INPUT IMPEDANCE OF A LINEAR TRANSFORMER (REFLECTED IMPEDANCE)
is the whole secondary loop impedance, load included. does not depend on the dot positions ( enters squared), and its reactance has the opposite sign to that of : an inductive secondary reflects as a capacitive reactance.
INPUT INDUCTANCE WITH THE SECONDARY SHORT-CIRCUITED
Lossless coils, from with . With the secondary open, the input is simply ; comparing the two measurements gives .
IDEAL TRANSFORMER: VOLTAGE AND CURRENT RATIOS
With the convention above. If one dot is moved to the other end of its winding while the voltage and current references stay on the same physical terminals, both ratios change sign: and . In the two-port convention ( entering the secondary dot) the current relation reads .
IMPEDANCE REFLECTION THROUGH AN IDEAL TRANSFORMER
connected across the secondary; independent of the dot positions. In the other direction, an impedance on the primary side appears on the secondary side as .
POWER CONSERVATION IN AN IDEAL TRANSFORMER
It neither stores nor dissipates energy: complex power in equals complex power out (convention above).
MAXIMUM POWER TRANSFER THROUGH AN IDEAL TRANSFORMER
Resistive source on the primary, resistive load on the secondary, . The load then receives , with the rms source voltage.
Two-port networks
Read the notesZ (OPEN-CIRCUIT IMPEDANCE) PARAMETERS
All four are in ohms, and each is measured with the other port open. and are driving-point (input and output) impedances. and are transfer impedances.
Y (SHORT-CIRCUIT ADMITTANCE) PARAMETERS
All four are in siemens, and each is measured with the other port shorted. whenever both exist. In general , because the two are measured under different terminations.
H (HYBRID) PARAMETERS
is the short-circuit input impedance (ohms), the open-circuit reverse voltage gain, the short-circuit forward current gain, and the open-circuit output admittance (siemens). Port 2 is shorted for and ; port 1 is open for and .
G (INVERSE HYBRID) PARAMETERS
whenever both exist. is the open-circuit input admittance (siemens), the short-circuit reverse current gain, the open-circuit forward voltage gain, and the short-circuit output impedance (ohms).
ABCD (TRANSMISSION) PARAMETERS
Written out, and . and are dimensionless, is in ohms and in siemens. and are measured with port 2 open, and with port 2 shorted. The minus sign is there because is the current that leaves port 2 and enters whatever is connected to it.
CONDITION FOR RECIPROCITY
Any one of these implies all the others (for the sets that exist). A reciprocal two-port has only three independent parameters.
CONDITION FOR SYMMETRY
These express electrical symmetry of the two ports, and they hold whether or not the network is reciprocal. For a network that is also reciprocal, only two parameters are independent (for example and ). Ports that can be swapped with no change at all need both and .
DETERMINANTS AND QUICK IDENTITIES
Use for a quick reciprocity check from any set. The determinant of a product is the product of the determinants, so after multiplying the ABCD matrices of reciprocal sections (built from , , , coupled coils and ideal transformers), must still equal 1. That catches arithmetic slips.
Z AND ABCD
exists only if ; exists only if .
Y AND ABCD
exists only if ; exists only if .
H FROM Z AND FROM Y
Note the pairs that are true reciprocals, each pair measured under the same termination: (port 2 shorted), (port 1 open), (port 2 open) and (port 1 shorted).
G FROM Z, FROM Y AND FROM ABCD
is the open-circuit forward voltage gain. exists only if (equivalently ).
T NETWORK AND T EQUIVALENT
is the series arm at port 1, the series arm at port 2, and the shunt arm to the common terminal. Every reciprocal two-port that has a has this T equivalent, though an arm may come out negative (not realisable with positive elements). The T joins the two lower terminals, so it is equivalent only in its port voltages and currents.
PI NETWORK AND PI EQUIVALENT
is the shunt arm at port 1, the shunt arm at port 2, and the series arm between the upper terminals. Every reciprocal two-port that has a has this equivalent, with the same caveats as the T.
COUPLED COILS
Coil across port 1 and coil across port 2, mutual inductance , with both dots at the upper terminals, so both port currents enter dotted terminals. Moving one dot to its lower terminal changes to everywhere. In the -domain replace by . The T equivalent (which may need a negative inductance) holds only if the two lower terminals may be joined.
SYMMETRIC LATTICE
Series arms join upper terminal to upper terminal and lower terminal to lower terminal; cross arms join each upper terminal to the lower terminal of the other port. Its transfer impedance changes sign when .
PARAMETER ADDITION
Valid only when each sub-network still satisfies the port condition after the connection (see the validity note below).
CASCADE CONNECTION
is the section nearer the source; keep the order. Always valid, because the current leaving is exactly the current entering . That is why the minus sign is built into the ABCD definition.
INPUT IMPEDANCE OF A TERMINATED TWO-PORT
Port 2 terminated in (so ). As this becomes , the open-circuit input impedance; at it becomes , the short-circuit input impedance.
VOLTAGE AND CURRENT GAIN WITH A LOAD
Same termination, with port 1 driven directly by . The current delivered to the load is , so the load-current gain is . With the output open, .
THEVENIN EQUIVALENT AT PORT 2
Port 1 driven by in series with . For , set to zero, which leaves across port 1. With and fixed, the load receives maximum power when .
OPEN- AND SHORT-CIRCUIT IMPEDANCES
Each is measured at one port with the other port open (oc) or shorted (sc). For any two-port, . So only three of the four are independent.
IMAGE IMPEDANCES
The image impedances are the pair for which terminating port 2 in makes the input impedance at port 1 equal to , and terminating port 1 in makes the impedance at port 2 equal to . For a symmetric network both equal the characteristic impedance : a load is reproduced at the input. For a reciprocal network the image transfer constant satisfies , which becomes when the network is also symmetric.
Balanced three-phase circuits
Read the notesBALANCED POSITIVE-SEQUENCE (ABC) SET
Phase b lags phase a by and phase c lags phase b by . For negative sequence (acb) the angles of and are interchanged: , .
OPERATOR A AND THE ZERO SUM OF A BALANCED SET
For abc: and . Hence any balanced set sums to zero, , and the same holds for a balanced set of currents.
STAR: LINE AND PHASE RELATIONS (ABC)
Each line voltage leads the phase voltage of its first subscript by ( leads , leads ). For negative sequence the magnitudes are unchanged but .
DELTA: LINE AND PHASE RELATIONS (ABC)
Phase currents , , are taken in the direction of their subscripts; each line current lags, by , the phase current leaving that line's corner ( lags , lags ). For negative sequence, .
BALANCED STAR-DELTA CONVERSION
Identical impedances only. The division is by a real number, so the impedance angle , and hence the power factor, is unchanged.
THREE-PHASE ACTIVE POWER
Balanced load, star or delta; rms values; = angle of the per-phase impedance. Pair the delta resistance with the delta phase current, or the star-equivalent resistance with the line current.
THREE-PHASE REACTIVE POWER
(absorbed) for an inductive, lagging load; for a capacitive, leading load.
COMPLEX AND APPARENT POWER, POWER FACTOR
and are the phasors of the same phase and is the complex conjugate. is in VA (or kVA); a three-phase kVA figure means this total for all three phases, not the per-phase value.
INSTANTANEOUS POWER OF A BALANCED LOAD
Balanced sinusoidal voltages and a balanced load; , rms. The total does not vary with time and equals the average power .
TWO-WATTMETER SUM (ANY THREE-WIRE LOAD)
Readings are taken with their signs. Valid for balanced and unbalanced three-wire loads.
WATTMETER READINGS FOR A BALANCED LOAD
Balanced sinusoidal system. The current coils, in lines a and c, carry the line currents towards the load; the pressure coils measure and (each coil's terminal on its own current-coil line, the other end on line b). For abc sequence the meter in line c reads and the meter in line a reads . The formulas hold for either sign of ( lagging, leading), so a leading load, or a reversed sequence, swaps which meter reads more.
READINGS IN TERMS OF P AND Q (BALANCED LOAD)
The same pair written with and ; handy for predicting the readings when and (or and the power factor) are given. exactly when , i.e. .
POWER-FACTOR ANGLE AND REACTIVE POWER FROM THE READINGS
Balanced load only. Follows from and . The two readings alone fix ; whether the load lags or leads needs either the nature of the load or knowledge of which physical meter reads , which depends on the connection and the phase sequence.
POWER FACTOR DIRECTLY FROM THE READINGS
Balanced load; the same content as the form. Insert a negative reading with its sign.
THREE-WATTMETER AND ONE-WATTMETER METHODS
Three-wattmeter method: one meter per line, each pressure coil from its line to the neutral, so each meter reads one phase power; valid for balanced and unbalanced loads. One-wattmeter method: for a balanced load, a single meter with its current coil in one line and its pressure coil from that line to the neutral (or to an artificial neutral formed by three equal impedances, one of them the pressure coil) reads one-third of the total.
CAPACITOR KVAR REQUIRED
Total for all three phases; is the original angle and the target angle, both lagging. For a unity target, equals the original .
CAPACITANCE PER PHASE OF THE BANK
= line voltage (rms), . Each star capacitor sees and supplies ; each delta capacitor sees the full and supplies .
NEUTRAL-SHIFT VOLTAGE (UNBALANCED STAR, NO NEUTRAL)
Nodal equation at N', with the source phase voltages measured from N; any line impedance is included in . It is zero when , which recovers the balanced case. If N' and N are joined through a neutral impedance , add to the denominator.