FOUNDATION · CHAPTER 1 OF 8

What one feedback loop does

Derives the gain of one negative-feedback loop from its two summing-junction equations. Then shows what the loop does to a drifting gain, a disturbance and sensor noise, and what high loop gain can cost. These results apply wherever an engineer closes a loop.

Updated 13 Oct 2026

What you will be able to do

You will derive the closed-loop gain of a feedback loop from its two summing-junction equations. You will see how loop gain shrinks the effect of a drifting gain and of a disturbance. You will see why the sensor's own error and noise reach the output almost untouched. You will see what high loop gain can cost: in some loops it brings instability.

Before you start

  1. Solving two linear equations in two unknowns

  2. The quotient rule for derivatives

  3. Complex numbers: magnitude, angle and cube roots

  4. The Laplace transform; a transfer function , output over input with zero initial conditions

  5. Poles of a rational transfer function with real coefficients (complex poles come in conjugate pairs); BIBO stability, bounded input giving bounded output, which holds exactly when every pole is in the open left half-plane

The loop in two equations

A negative-feedback loop measures the output through a sensor and subtracts the sensor signal from the reference. What is left drives the forward path. The output is the value at which both statements hold. With transfer functions the algebra is the same: at each away from poles, every transfer function is just a complex number.

THE TWO SUMMING-JUNCTION EQUATIONS

Negative feedback, zero initial conditions, inputs applied at ; unilateral Laplace transform, lower limit (for a signal zero before the bilateral form agrees); , the imaginary unit. reference, output, actuating signal, forward gain, sensor gain. With , is the transform of the error . Example signals are in volts; constant gains are dimensionless.

CLOSED-LOOP GAIN

Holds when . is the closed-loop gain. The product is the loop gain: the gain met once round the loop, dimensionless.

GAIN WHEN THE LOOP GAIN IS LARGE

The first form is exact for ; the approximation needs . With positive constant gains, falls short of by the fraction of . has nearly dropped out: the sensor gain sets the output.

WATCH OUT FOR

Loop gain is not . The test: multiply every gain met once round the loop. With and , , not 100.

WORKED EXAMPLE

A loop with negative feedback has and . The reference is . Find , and , and check the result against .

Solution
  1. Loop gain: . This is the number that appears in the denominator.

  2. Closed-loop gain: . Feedback has cut the gain from 100 to 9.09.

  3. Output: , since is output over reference.

  4. Actuating signal: : the reference minus the sensor signal.

  5. Check: . Both equations hold at once, as they must.

  6. Compare with : is 9.1% below it, the fraction .

Answer: , , . A small actuating signal, amplified by , gives the full output.

How much a drifting gain matters

Forward gains drift with temperature, supply and age. Sensitivity asks: if changes by a small fraction, by what fraction does change? It is the ratio of the two fractional changes, found by differentiating with respect to .

SENSITIVITY OF THE CLOSED-LOOP GAIN TO G

Small changes of with fixed; constant gains, . is dimensionless. With no feedback (), : drifts one for one with .

SENSITIVITY OF THE CLOSED-LOOP GAIN TO H

Small changes of with fixed; constant gains, . For this is close to : a 1% error in the sensor gain gives about a 1% error in , in the opposite direction. The loop cannot correct what it measures wrongly.

Forward gain

Change in

Closed-loop ()

Change in

100

0

9.091

0

80

-20%

8.889

-2.2%

120

+20%

9.231

+1.5%

A 20% fall in moves by only 2.2%, and a 20% rise by 1.5%. The sensitivity at , , predicts 20% divided by 11, that is 1.8%, for both. The figures differ because is the slope at one point and curves.

WATCH OUT FOR

Using for a large change. The test: recompute at the new and compare, as the table does.

Disturbance, sensor noise and the price

A disturbance enters the loop after some forward gain, for instance a load acting on the plant. The loop sees its effect at the output and pushes back. Sensor noise is different. It enters at the sensor, so the loop takes it for a true reading of the output and obeys it. Both transfer functions follow from the same two equations, with the extra signal added at its own point.

DISTURBANCE TO OUTPUT

; the loop is linear, so the effects of and add. Holds when . (volts) is added at the input of the plant ; is the controller before it. Loop gain . With no feedback (), : the loop divides the disturbance's effect by .

SENSOR NOISE TO OUTPUT

Holds when . (volts) is added to the sensor output . The output carries with exactly the gain that it gives , so . For , : the sensor's error, read in output units, reaches the output in full.

WORKED EXAMPLE

A loop with negative feedback has controller , plant and sensor . A disturbance is added at the plant input, between controller and plant. Separately, noise is added to the sensor output. With , find the output in each case.

Solution
  1. Loop gain: , so . Both transfer functions share this denominator.

  2. Disturbance: . So .

  3. Without feedback the same disturbance would give , so the loop has cut its effect by a factor of 11.

  4. Noise: the forward path is , so .

  5. So . The noise is a tenth the size of the disturbance but moves the output just as far.

Answer: Disturbance: . Noise: . The loop suppresses the disturbance but passes the noise at gain .

WATCH OUT FOR

Thinking more loop gain quiets sensor noise too. The test: write and compare it with . They are equal in size, and both stay near for any .

Each benefit above is a division by , so it is tempting to raise the gain without limit. A real forward path has lags, so depends on . Suppose at some () with and finite there: then , so , nothing cancels, and has a pole on the axis. For its conjugate sits at , and a simple pair puts an undamped sinusoid at in the response.

CONDITION FOR A CLOSED-LOOP POLE ON THE IMAGINARY AXIS

, finite at , in rad/s; the angle is taken modulo and written as a lag. LHP and RHP are the open left and right half-planes; the axis is in neither. No closed-loop pole in the RHP and only simple poles on the axis: the loop is marginally stable, which is not BIBO stable (a pole lies outside the LHP).

THREE EQUAL LAGS WITH UNITY FEEDBACK

, with the loop gain at (dimensionless); in rad/s, so lies between and . The closed-loop poles solve : has size at angles , and .

Closed-loop poles

Stability

0

-1 (three times)

stable

2

-2.26 and -0.37 ± j1.09

stable

8

-3 and ± j1.73

marginally stable, not BIBO stable

16

-3.52 and 0.26 ± j2.18

unstable, two poles in the RHP

As rises, the complex pair moves right and crosses the axis at , as the condition predicts. Not every loop does this. With or , , the angle of stays above at every finite and , so the poles start in the LHP at and never reach the axis, for any . In the three-lag loop, whose lag reaches , high loop gain buys insensitivity to and to disturbances at the cost of stability.

Check yourself

CHECK YOURSELF 1

A loop with negative feedback has constant gains and . What is the closed-loop gain ?

  1. (A)

    4.55

  2. (B)

    5.00

  3. (C)

    10.0

  4. (D)

    50

Answer and solution

Answer: (A)

  1. Loop gain: .

  2. .

  3. The value is only the large-loop-gain approximation; falls short of it by the fraction , so B is not exact.

CHECK YOURSELF 2

A loop with negative feedback has constant gains and . Find the sensitivity of the closed-loop gain to . Give a number.

Answer and solution

Answer: (accepted range )

  1. .

  2. .

  3. .

CHECK YOURSELF 3

A loop with negative feedback has controller , plant and sensor . A disturbance is added at the plant input, between controller and plant. With , find . Give a number.

Answer and solution

Answer: (accepted range )

  1. Loop gain: .

  2. .

  3. .

Used in these GATE topics