GATE 2023 EE Q.64: solution and answer

GATE 2023 · EEQ.64 · 2 marks · NAT

A balanced delta connected load consisting of the series connection of one resistor () and a capacitor () in each phase is connected to three-phase, 50 Hz, 415 V supply terminals through a line having an inductance of per phase, as shown in the figure. Considering the change in the supply terminal voltage with loading to be negligible, the magnitude of the voltage across the terminals in Volts is ________ (Round off to the nearest integer).

GATE 2023 EE question 64: Three supply terminals on the left, labelled '3-phase, 50 Hz, 415 V (r.m.s.) supply terminals'.Tap to open full size
Figure from the GATE 2023 EE paper. It is part of the question.
Figure description

Three supply terminals on the left, labelled '3-phase, 50 Hz, 415 V (r.m.s.) supply terminals'. Each supply terminal connects through a series line inductor L to a load terminal: top line to terminal A, middle line to terminal B, bottom line to terminal C. At the load, three identical branches, each a resistor R in series with a capacitor C, are connected in delta: one R-C branch between A and B, one between B and C, and one between C and A (the C-A branch is drawn with a return wire from the right side back up to A). Values printed below the figure: R = 15 Ω, L = 31.83 mH, C = 212.21 μF.

Answer and solution

ANSWER

.

Official answer: 414 to 416Source: Official answer key, GATE 2023 EE (IIT Kanpur)

  1. Reactances at : , and .

  2. Impedance of each delta branch (R in series with C): .

  3. The load is balanced, so replace the delta with an equivalent star: per phase.

  4. Per-phase equivalent circuit (supply neutral to the load's equivalent star point ): the line inductance is in series with , so , and .

  5. The supply terminal voltage does not change with loading, so the supply phase voltage stays at . Line current: .

  6. Voltage across one phase of the equivalent star load: . The voltage-divider ratio shows the same thing: , whose magnitude is .

  7. Line voltage at the load terminals: . In magnitude, the capacitive load exactly cancels the drop across the line inductance. Only the phase changes: the load voltage lags the supply voltage by .

KEY IDEA

Convert the balanced delta load to an equivalent star () and solve a single-phase circuit: a stiff source, then of line reactance, then the star-phase load. The divider ratio has magnitude 1. So the load line voltage has the same magnitude as the supply (415 V) and lags it by .

WATCH OUT FOR

Putting the line inductance in series with the delta branch impedance without converting to star first, i.e. . Line elements carry line current, so they can only be combined with the per-phase star equivalent . The second trap is assuming a series line inductance must lower the load voltage. With a capacitive load there can be no drop at all, or even a rise. Here the magnitude is unchanged.

From the GATE 2023 EE paper. Every question of this paper · Download the full paper · All 11 Three-phase (EE) questions, with notes