A balanced delta connected load consisting of the series connection of one resistor () and a capacitor () in each phase is connected to three-phase, 50 Hz, 415 V supply terminals through a line having an inductance of per phase, as shown in the figure. Considering the change in the supply terminal voltage with loading to be negligible, the magnitude of the voltage across the terminals in Volts is ________ (Round off to the nearest integer).
Tap to open full sizeFigure description
Three supply terminals on the left, labelled '3-phase, 50 Hz, 415 V (r.m.s.) supply terminals'. Each supply terminal connects through a series line inductor L to a load terminal: top line to terminal A, middle line to terminal B, bottom line to terminal C. At the load, three identical branches, each a resistor R in series with a capacitor C, are connected in delta: one R-C branch between A and B, one between B and C, and one between C and A (the C-A branch is drawn with a return wire from the right side back up to A). Values printed below the figure: R = 15 Ω, L = 31.83 mH, C = 212.21 μF.