The whole Electrical Machines formula sheet, to print
77 formulas in 5 topics, each with when to use it. Each is explained in the topic notes.
IAE Academy: Electrical Machines formula sheet (GATE EE, IN)
Transformers: single-phase, three-phase and auto-transformers
Read the notesEMF EQUATION (RMS INDUCED VOLTAGE OF A WINDING)
in V, in Hz, = turns of that winding, = peak core flux in Wb (, with the net iron cross-section). The derivation assumes the core flux is sinusoidal. It applies to the primary and secondary separately, each with its own .
IDEAL TRANSFORMER RELATIONS
An ideal transformer has no winding resistance, no leakage flux, no core loss and an infinitely permeable core, so it needs no magnetising current. In a practical transformer, holds only approximately (closest at no load), and holds only when the no-load current is neglected.
COMPONENTS OF CORE LOSS
= hysteresis loss (the Steinmetz exponent is empirical, commonly taken as 1.6). = eddy-current loss, where is the lamination thickness. With : at constant , and . At constant , . At constant , does not depend on , and .
REFERRING SECONDARY QUANTITIES TO THE PRIMARY
Here . To refer a primary quantity to the secondary, use the inverse: , , . An impedance always grows when it is referred to the side with more turns.
TOTAL SERIES IMPEDANCE REFERRED TO EACH SIDE
and . In the approximate equivalent circuit the shunt branch ( in parallel with ) is moved to the supply terminals, ahead of the series impedance. This is justified because the no-load current is a small fraction of rated current.
SHUNT BRANCH FROM THE OC TEST (REFERRED TO THE TESTED SIDE)
These values hold at the voltage and frequency of the test. Core loss is not linear in flux, so and are not constants at other voltages.
SERIES IMPEDANCE FROM THE SC TEST (REFERRED TO THE ENERGISED SIDE)
and are referred to the energised winding. Multiply or divide by before combining them with quantities on the other side.
COPPER LOSS AT ANOTHER CURRENT, AND PERCENTAGE IMPEDANCE
If the SC test was not run at rated current, scale its reading by the square of the current ratio to get the full-load copper loss. is the SC-test voltage at rated current, expressed as a percentage of rated voltage. It has the same value whichever side it is calculated on, provided , and all belong to that side.
DEFINITION
is the no-load secondary voltage and the full-load (rated) secondary voltage. Some texts divide by instead ("regulation down"). These notes use the rated full-load voltage as the base.
APPROXIMATE (FIRST-ORDER) REGULATION
Use for a lagging and for a leading power factor. and are the rated current and voltage on the same side as , (that is, , with primary quantities, or , with secondary quantities). and are the percentage resistance and reactance. The formula neglects the quadrature component of the drop.
CONDITION FOR ZERO REGULATION (FIRST-ORDER FORMULA)
Zero regulation is possible only at a leading power factor, where the resistive drop in phase with is cancelled by the component of the reactive drop. At any leading power factor more leading than this, the regulation is negative: the terminal voltage rises on load.
CONDITION FOR MAXIMUM REGULATION
Obtained by setting . Maximum regulation occurs when the load power-factor angle equals the impedance angle of the series impedance, and its value is then the percentage impedance.
EFFICIENCY AT LOAD FRACTION X
is the rated VA. is the output. is the constant core loss (from the OC test at rated voltage). is the full-load copper loss (from the SC test at rated current). The formula assumes the terminal voltage stays at its rated value.
MAXIMUM EFFICIENCY (AT A GIVEN POWER FACTOR)
Efficiency is highest at the load where the variable copper loss equals the constant core loss. That load is VA, or . The load fraction does not depend on power factor. The value of does: it is highest at unity power factor.
ALL-DAY (ENERGY) EFFICIENCY
This is the ratio of energy output to energy input over 24 hours, with in hours and . The core loss is counted for all 24 h, including no-load periods, because it is present whenever the transformer is energised. Copper loss is counted only for the hours the transformer carries each load.
LOAD SHARING BETWEEN TWO PARALLELED TRANSFORMERS (EQUAL VOLTAGE RATIOS)
and are complex ohmic impedances referred to the same side. and are per-unit impedances, each on its own transformer's rating. Each unit's share is inversely proportional to its ohmic impedance. The share is proportional to its rating only when . The unit with the lower per-unit impedance takes more than its proportional share and reaches full load first.
POWER CONDUCTED AND POWER TRANSFORMED
The common winding carries and the series winding carries . Only passes through transformer action, so the windings and core need only be sized for .
COPPER SAVING COMPARED WITH A TWO-WINDING TRANSFORMER
This compares the same output and the same voltages, with the same current density and the same mean length of turn in both designs. The saving approaches 100% as and is small for large ratios. For example, saves 50% and saves only 25%.
TWO-WINDING TRANSFORMER RECONNECTED AS AN AUTO-TRANSFORMER
Each winding keeps its rated voltage and current, so the inductively transformed power equals the two-winding rating . The auto-transformer's losses are the same as the two-winding transformer's, but its output is larger, so its efficiency is higher. Its per-unit series impedance on its own rating is times that of the two-winding transformer. This gives lower regulation and a higher short-circuit current.
Energy conversion and DC machines
Read the notesFORCE, CONSTANT-CURRENT FORM
Coenergy is written as a function of and , and the partial derivative is taken with held fixed. This form is convenient when the excitation current is known.
FORCE, CONSTANT-FLUX-LINKAGE FORM
Field energy is written as a function of and , and the partial derivative is taken with held fixed. Note the minus sign. This gives the same force as the constant-current form.
TORQUE
This is the rotational analogue of the force expressions. is the mechanical angle in radians and is in N m.
LINEAR (UNSATURATED) SINGLY EXCITED CASE
This applies when the system is magnetically linear, so that . The force acts in the direction that increases the inductance, i.e. that reduces the reluctance of the magnetic path.
DOUBLY EXCITED SYSTEM (MAGNETICALLY LINEAR)
The first two terms are reluctance torques. They exist only if a self-inductance varies with (saliency). The third term is the mutual (alignment) torque, which needs both windings excited. In a machine with a uniform air gap only the mutual term survives.
GENERATED EMF
- = number of poles
- = flux per pole (Wb)
- = total number of armature conductors
- = speed (rpm)
- = number of parallel paths: for a simplex lap winding, and for a simplex wave winding whatever the value of
ELECTROMAGNETIC TORQUE
is the total armature current. With in Wb and in A, is in N m. , and are the same as in the EMF equation.
COMPACT FORM
is the mechanical angular speed in rad/s. is a fixed constant of the winding, so both and are proportional to .
ELECTROMAGNETIC POWER AND TORQUE
The electromagnetic (developed) power equals the electromagnetic torque times the speed, in both modes. Shaft power differs from it by the rotational (core and mechanical) losses.
TERMINAL VOLTAGE EQUATIONS
is the resistance of the armature circuit. It includes the series-field (and interpole) winding resistance where those windings carry , as in series and long-shunt compound machines. The brush contact drop is treated as a constant voltage when one is given, and neglected otherwise. It is subtracted for a generator and added for a motor.
CURRENTS IN A SHUNT MACHINE
is the line (load or supply) current and is the total resistance of the shunt field circuit. In a series machine, .
VOLTAGE REGULATION (GENERATOR) AND SPEED REGULATION (MOTOR)
Both are referred to the full-load value. A flat-compounded generator has zero voltage regulation.
SPEED EQUATION
This follows directly from , with in rpm. For two operating points of the same machine, . Every speed-control method below can be reasoned from this equation.
EFFICIENCY
For a generator, the output is electrical terminal power and the input is mechanical shaft power. For a motor it is the reverse.
CONDITION FOR MAXIMUM EFFICIENCY
Efficiency is maximum when the variable copper loss equals the constant losses.
- Exact when the terminal voltage is constant and the same current flows as output current and through . Example: a separately excited generator, with and .
- Approximate for shunt machines, where . It is used there with .
ARMATURE-REACTION AMPERE-TURNS PER POLE (BRUSH SHIFT)
is the brush shift from the geometric neutral axis in mechanical degrees, and is the current in each conductor. With no brush shift, and all armature ampere-turns per pole are cross-magnetising.
Three-phase and single-phase induction machines
Read the notesSYNCHRONOUS SPEED (RPM)
= supply frequency (Hz), = number of poles. This is the speed of the rotating stator field. In rad/s: .
AMPLITUDE OF THE RESULTANT ROTATING MMF (THREE-PHASE)
is the peak MMF of one phase winding. Holds for a balanced three-phase winding carrying balanced three-phase currents. The resultant has constant amplitude and rotates at .
SLIP
Dimensionless. at standstill and near synchronous speed. : motoring. : the rotor is driven above (induction generator). : the rotor turns against the field (braking, as in plugging).
ROTOR (INDUCED) FREQUENCY
Frequency of the currents induced in the rotor at slip , where is the stator supply frequency. At standstill (), .
SPLIT OF THE ROTOR BRANCH RESISTANCE
The fixed part dissipates rotor copper loss. The slip-dependent part is the equivalent load resistance, and the power it absorbs is the gross mechanical power developed, per phase.
ROTOR CURRENT REFERRED TO THE STATOR (APPROXIMATE CIRCUIT)
Per-phase rms rotor current, with the per-phase voltage. The stator current is the phasor sum of and the no-load (magnetizing) current.
AIR-GAP POWER SPLIT
is the total air-gap power, the total rotor copper loss and the gross mechanical power. The split gives rotor power quantities without computing currents. Since , the motor's overall efficiency cannot exceed .
DEVELOPED (ELECTROMAGNETIC) TORQUE
is the total three-phase air-gap power and the synchronous speed in rad/s. is the rotor speed in rad/s. Divide air-gap power by synchronous speed, or mechanical power by rotor speed, and never mix the two. Shaft torque is lower by the rotational-loss torque.
TORQUE IN TERMS OF APPLIED VOLTAGE
Approximate equivalent circuit. is the per-phase stator voltage. For the exact circuit use the Thevenin values in place of .
SLIP AT MAXIMUM TORQUE
Approximate equivalent circuit. Independent of the applied voltage and proportional to . Adding rotor resistance moves the maximum-torque point towards standstill.
MAXIMUM (PULL-OUT OR BREAKDOWN) TORQUE
Approximate equivalent circuit. Independent of : changing the rotor resistance moves where the maximum torque occurs, not its value. Proportional to .
STARTING TORQUE ($S=1$)
The general torque expression with .
TORQUE RELATIVE TO MAXIMUM TORQUE
Valid when the stator resistance is neglected (), so that . The same supply voltage and frequency apply to and .
QUANTITIES FROM THE NO-LOAD TEST
and are line values and is the total three-phase input power. Per-phase values are taken for an equivalent star connection. The second relation uses the low power factor (impedance almost entirely reactive).
PARAMETERS FROM THE BLOCKED-ROTOR TEST
and are line values and is the total three-phase input power. Results are per phase for an equivalent star connection. If the test is run at a reduced frequency , multiply the reactance by . The test cannot separate from , so a split (often equal) must be assumed or given.
STARTING TORQUE RELATIVE TO FULL-LOAD TORQUE
From with constant and the magnetizing current neglected. is the DOL (full-voltage) starting current, the full-load current, the full-load slip. for DOL, for star-delta, and = tap ratio for an autotransformer.
ROTOR RESISTANCE FOR MAXIMUM STARTING TORQUE
Wound-rotor motor, approximate equivalent circuit. is the added rotor resistance referred to the stator. This choice makes .
SLIPS RELATIVE TO THE FORWARD AND BACKWARD FIELDS
is the rotor speed in the forward direction. At standstill and , so the net torque .
Synchronous machines
Read the notesSYNCHRONOUS SPEED
in rpm, = supply or generated frequency in Hz, = number of poles. In steady-state operation the rotor and the rotating armature field both turn at this speed. Unlike an induction machine, there is no slip.
GENERATED EMF PER PHASE
= winding factor (), = fundamental flux per pole (Wb), = series turns per phase. All quantities are per-phase RMS values of the fundamental, for sinusoidally distributed flux.
PITCH (COIL-SPAN) FACTOR
= the angle, in electrical degrees, by which the coil span falls short of full pitch (). For a full-pitch coil, and .
DISTRIBUTION (BREADTH) FACTOR
= slots per pole per phase. = slot pitch in electrical degrees .
PHASOR VOLTAGE EQUATION, GENERATOR (CYLINDRICAL ROTOR)
All quantities are per-phase phasors, and is the imaginary unit. lags by the power-factor angle for a lagging load and leads it for a leading load. The equation is valid for a round rotor, where a single applies whatever the rotor position.
PHASOR VOLTAGE EQUATION, MOTOR (CYLINDRICAL ROTOR)
Motor convention: is the current drawn from the supply and is the back emf. In motoring operation lags by the load angle .
PERCENTAGE VOLTAGE REGULATION
= the terminal voltage on no load, with the field current and speed unchanged, when that field current gives rated at the specified load. = rated terminal voltage. Both are per phase. Regulation is positive for lagging-pf loads (the terminal voltage falls on loading) and can be zero or negative for leading-pf loads.
SHORT-CIRCUIT RATIO (SCR)
Here is the saturated direct-axis (synchronous) reactance in per unit, taken from the OCC at rated voltage. A higher SCR means a smaller synchronous reactance, a larger maximum power (), better steady-state stability and a smaller voltage change with load, at the cost of a larger machine.
POWER-ANGLE EQUATION (CYLINDRICAL ROTOR, $R_A \APPROX 0$)
Per-phase power in W, with per-phase and . Multiply by 3 for the total 3-phase power. Valid for round-rotor machines only. For a generator, when leads .
PHASOR EQUATION, SALIENT-POLE GENERATOR ($R_A \APPROX 0$)
Per phase. lies along the q-axis. and are the components of perpendicular to and along .
LOAD ANGLE AND EXCITATION EMF FROM TERMINAL CONDITIONS (SALIENT-POLE GENERATOR, $R_A \APPROX 0$, LAGGING PF)
Per phase. = power-factor angle (lagging). Method: form , whose angle is , then add along the same direction to get . For a leading pf, replace with .
POWER-ANGLE EQUATION (SALIENT POLE, $R_A \APPROX 0$)
Per phase. The first term is the excitation power: it has the same form as for a round rotor, with in place of . The second term is the reluctance power. It arises only from saliency () and is present even with zero excitation (). With it is the only term, and its maximum is at . With and , maximum power occurs at some that depends on the excitation.
SLIP TEST FOR $X_D$ AND $X_Q$
Per phase. The rotor is driven slightly away from synchronous speed with the field winding open, and a reduced balanced 3-phase voltage is applied to the armature. The armature voltage and current swing slowly. and occur when the armature mmf lies along the d-axis, and and when it lies along the q-axis.
SYNCHRONIZING POWER COEFFICIENT
Per phase, cylindrical rotor, , in W per electrical radian at operating angle . It is the restoring power per unit change in when synchronism is briefly disturbed. Stable operation needs , which is why a cylindrical rotor is limited to .
Losses and efficiency of electric machines
Read the notesHYSTERESIS LOSS (STEINMETZ'S LAW)
is a material constant and is the core volume. The exponent (the Steinmetz coefficient) depends on the core material, and 1.6 is the classical value. A problem will state the exponent to use, or will say only that at constant .
EDDY CURRENT LOSS
is the lamination thickness, and (core resistivity). This form assumes sinusoidal flux and thin laminations. At the same , and core volume, halving cuts to one quarter. This is why cores are laminated rather than solid.
TOTAL CORE LOSS VS. FREQUENCY
Valid only when is held constant across the tests. A core-loss separation test is designed exactly this way.
WHY B_MAX FOLLOWS V/F (SINUSOIDAL SUPPLY)
is the number of turns of the winding and the net core area. The winding resistance and leakage drops are neglected, so . If and are changed in the same ratio (constant ), stays fixed.
CORE-LOSS SCALING WITH SUPPLY VOLTAGE AND FREQUENCY (SAME WINDING)
Follows from . At constant voltage, the eddy current loss does not depend on frequency, and the hysteresis loss falls as frequency rises (with a Steinmetz exponent of 1.6).
EFFICIENCY (GENERAL)
Applies to any machine: motor, generator or transformer. Express , and every loss in the same unit (W or kW). The last form is convenient for a motor, when the electrical input is known.
CONDITION FOR MAXIMUM EFFICIENCY
Assumes the output is proportional to the load current (fixed terminal voltage and power factor), a constant loss that does not depend on load, and a variable loss that scales as . Setting then gives the condition shown. Any loss that is proportional to (such as the DC brush-drop loss) drops out of the condition. For a transformer, the load (kVA) at which efficiency is maximum does not depend on power factor. The value of does depend on it, and is highest at unity power factor.
LOAD FRACTION (AND CURRENT) FOR MAXIMUM EFFICIENCY
is the fraction of rated (full) load, the constant loss, and the full-load variable () loss. Valid when the constant loss stays fixed and the variable loss scales as . For a transformer, the load at maximum efficiency is (kVA).
ALL-DAY (ENERGY) EFFICIENCY OF A TRANSFORMER
Output energy over input energy across 24 hours. is the time in hours spent at load fraction , with output . The core loss applies for all 24 h while the transformer is energised, even at no load. The copper loss applies only while the transformer carries load.
INDUCTION MOTOR POWER SPLIT
is the per-unit slip, with rpm. is the power crossing the air gap: stator input minus stator copper and stator iron losses. The ratio holds for three-phase totals, or per phase if used consistently. So and . Shaft output = − friction and windage − stray load loss. Because of this chain, efficiency can never exceed , and in practice is below it.