The HMI (human-machine interface) is what the operator sees; three kinds of screen do most of the work.
Priority, set at configuration from the consequence of ignoring the alarm and the time left to respond, orders the list: a critical alarm shows first and loudest. A noisy signal near a limit can raise and clear an alarm again and again (chatter). The cure is a deadband d below the high limit H: on at process value PV≥H, off only at PV≤H−d, last state kept in between. Take a steady true value x with noise within ±e. Chatter needs x+e≥H and x−e≤H−d, so H−e≤x≤H−d+e, possible only if d≤2e.
Older trends come from the historian, which logs each tag at its own interval Tlog, often slower than polling.
HISTORIAN STORAGE PER DAY
S=N⋅Tlog86400⋅b
Holds when every tag is logged at one constant interval, uncompressed. N is the number of tags, T_log the interval in s, b the bytes per sample, S in bytes per day; 86 400 s is one day.