IAE Academy

GATE 2023 EE Q.60: solution and answer

GATE 2023 · EEQ.60 · 2 marks · NAT

The two-bus power system shown in figure (i) has one alternator supplying a synchronous motor load through a Y-Δ transformer. The positive, negative and zero-sequence diagrams of the system are shown in figures (ii), (iii) and (iv), respectively. All reactances in the sequence diagrams are in p.u. For a bolted line-to-line fault (fault impedance = zero) between phases 'b' and 'c' at bus 1, neglecting all pre-fault currents, the magnitude of the fault current (from phase 'b' to 'c') in p.u. is ____________ (Round off to 2 decimal places).

GATE 2023 EE question 60: Figure (i): single-line diagram.Tap to open full size
Figure from the GATE 2023 EE paper. It is part of the question.
Figure description

Figure (i): single-line diagram. A grounded-Y alternator (with a reactor to ground) connects to bus 2; transformer T1 (grounded-Y on the bus 2 side, delta on the bus 1 side) connects bus 2 to bus 1; at bus 1 a synchronous motor (Y, grounded through reactance jXn) is connected. Figure (ii) positive sequence: Eg'' source in series with j0.1 up to bus 2; j0.1 between bus 2 and bus 1; at bus 1 a j0.3 reactance in series with the source Em'' returning to the reference. Figure (iii) negative sequence: same as (ii) but with no sources: j0.1 from bus 2 to reference, j0.1 between bus 2 and bus 1, j0.3 from bus 1 to reference. Figure (iv) zero sequence: at bus 2, j0.05 and j0.15 in series to reference; j0.1 between bus 2 and the transformer's zero-sequence break (the delta side is isolated from the line); at bus 1, j0.06 and j0.09 in series to reference, with no connection between the two sides.

Answer and solution

ANSWER

The magnitude of the line-to-line fault current is about 7.22 p.u.

Official answer: 7.1 to 7.3Source: Official answer key, GATE 2023 EE (IIT Kanpur)

  1. Neglecting pre-fault currents, both internal emfs are p.u., so the pre-fault voltage at bus 1 is p.u.

  2. Positive-sequence Thevenin impedance at bus 1 (sources shorted): the motor branch is in parallel with the path through the line and generator, .

  3. The negative-sequence network has the same topology and no sources, so p.u.

  4. A line-to-line fault between and carries no zero-sequence current, so and is not needed. With zero fault impedance, p.u.

  5. Fault current in phase : , and , so

KEY IDEA

For a line-to-line fault, only the positive and negative sequence networks are in series: , with and . The zero-sequence network is not needed.

WATCH OUT FOR

Including the zero-sequence impedance in the line-to-line fault (it belongs to the line-to-ground and double-line-to-ground faults). Another slip is forgetting the factor, or leaving out the motor branch when finding .

From the GATE 2023 EE paper. Every question of this paper · Download the full paper · All 8 Faults questions, with notes

More Faults questions