Harmonics & PF formulas
Line-current harmonics, power factor and distortion factor. 16 formulas for GATE EE, IN Power Electronics, each with when to use it. Each is explained in the topic notes.
IAE Academy: Line-current harmonics, power factor and distortion factor formulas (GATE EE, IN)
All 16 Harmonics & PF formulas
AVERAGE OUTPUT VOLTAGE, SINGLE-PHASE FULLY CONTROLLED BRIDGE
Continuous conduction, zero source inductance.
AVERAGE OUTPUT VOLTAGE, THREE-PHASE FULLY CONTROLLED BRIDGE
Continuous conduction, zero source inductance. At this is the diode bridge value .
RMS LINE CURRENT, THREE-PHASE BRIDGE
In each cycle a line carries for , nothing for , for , and nothing for . With an ideal ripple-free this does not depend on .
LINE CURRENT OF PHASE A (SIX-PULSE BRIDGE)
Reference . At the positive block is centred on the positive peak of . For the whole waveform is the waveform delayed by . The peak of the -th term is . Zero overlap, ripple-free .
RMS FUNDAMENTAL LINE CURRENT, THREE-PHASE BRIDGE
The peak of the fundamental is . Divide by for the rms value.
RMS OF THE N-TH HARMONIC, THREE-PHASE BRIDGE
Six-pulse bridge, zero overlap, ripple-free . Relative to the fundamental the magnitude falls as , and it does not depend on .
LINE CURRENT, SINGLE-PHASE FULLY CONTROLLED BRIDGE
Reference . The current is a square wave of delayed by , so every odd order is present. Ripple-free , zero overlap. The magnitudes do not depend on .
LINE CURRENT, SINGLE-PHASE HALF-CONTROLLED BRIDGE
Half-controlled bridge (semi-converter), or a full bridge with a freewheeling diode, with ripple-free . The line current is from to , zero while the load freewheels, then from to . Here the harmonic magnitudes do depend on , and the fundamental lags the supply voltage by .
DISPLACEMENT FACTOR
is the phase angle between the supply voltage and the fundamental line current. With zero overlap, for a fully controlled bridge and for a single-phase half-controlled bridge.
DISTORTION FACTOR
The ratio of the fundamental rms current to the total rms line current. DF .
INPUT POWER FACTOR
Sinusoidal supply voltage. For the three-phase case and . For the single-phase case and .
TOTAL HARMONIC DISTORTION OF THE LINE CURRENT
Harmonics are measured relative to the fundamental. Equivalently, .
SIX-PULSE BRIDGE, IDEAL INDUCTIVE LOAD
Fully controlled bridge, ripple-free , zero overlap. DF and THD do not change with . Only DPF does. A diode bridge () has PF .
SINGLE-PHASE HALF-CONTROLLED BRIDGE, IDEAL INDUCTIVE LOAD
Ripple-free , zero overlap. At this gives PF , the same as the full bridge. For its PF is higher than the full bridge's .
POWER AND REACTIVE POWER, THREE-PHASE FULLY CONTROLLED BRIDGE
Zero overlap, lossless converter. is the fundamental reactive power. With , the fundamental apparent power is .
OUTPUT VOLTAGE WITH OVERLAP, THREE-PHASE FULLY CONTROLLED BRIDGE
is the source inductance per phase, with ripple-free . For the single-phase fully controlled bridge the matching result is .
Where this was asked: 2018 (1), 2020 (1), 2022 (2), 2024 (1), 2025 (1). See the 6 previous-year questions on Harmonics & PF. This shows what was asked, not what will be asked.