A cylindrical rotor synchronous generator has steady state synchronous reactance of 0.7 pu and subtransient reactance of 0.2 pu. It is operating at pu terminal voltage with an internal emf of pu. Following a three-phase solid short circuit fault at the terminal of the generator, the magnitude of the subtransient internal emf (rounded off to 2 decimal places) is ______ pu.
GATE 2020 EE Q.49: solution and answer
Answer and solution
ANSWER
The magnitude of the subtransient internal emf is 1.02 pu.
Official answer: 1.01 to 1.03Source: Official answer key, GATE 2020 EE (IIT Delhi)
Because rotor flux linkages cannot change instantaneously at the instant of a fault, the emf behind the subtransient reactance must be evaluated using the prefault load current — first found from the steady-state circuit.
Prefault steady-state relation: , with , , .
Solve for the prefault current:
The subtransient internal emf is the emf behind the subtransient reactance, evaluated at this same prefault current: , with .
Compute:
Magnitude:
KEY IDEA
Flux linkages (and hence the emf behind the subtransient reactance) cannot change instantaneously at the instant of fault, so is computed using the prefault load current together with the subtransient reactance, evaluated at the prefault terminal voltage.
WATCH OUT FOR
Using the subtransient reactance to recompute a "prefault" current, or trying to use the given internal emf directly as , instead of first finding the actual prefault line current from the steady-state relation and then applying that same current with .
From the GATE 2020 EE paper. Every question of this paper · Download the full paper · All 11 Synchronous machines questions, with notes
More Synchronous machines questions
- GATE 2026 EE Q.20 · MCQ · 1 markA certain application requires power at a frequency of 16.67 Hz, while the available grid frequency is 50 Hz.
- GATE 2026 EE Q.22 · MCQ · 1 markThe figure shows the single-line diagram of a synchronous generator delivering P = 50 MW of power at unity…
- GATE 2025 EE Q.28 · MSQ · 1 markInstrument(s) required to synchronize an alternator to the grid is/are
- GATE 2025 EE Q.35 · NAT · 1 markThe induced emf in a 3.3 kV, 4 pole, 3-phase star connected synchronous motor is considered to be equal and…
