IAE Academy

4-20 mA & networks formulas

Instrument networks and the 4-20 mA transmitter. 8 formulas for GATE IN Sensors and Industrial Instrumentation, each with when to use it. Each is explained in the topic notes.

All 8 4-20 mA & networks formulas

MEASURED VALUE TO LOOP CURRENT

Linear transmitter, 4 mA at LRV and 20 mA at URV; I in mA.

LOOP CURRENT TO MEASURED VALUE

Inverse of the relation above; valid for 4 mA to 20 mA.

PERCENT OF SPAN FROM CURRENT

0 % at 4 mA, 50 % at 12 mA, 100 % at 20 mA.

RECEIVER VOLTAGE

A 250 Ω receiver turns 4 mA to 20 mA into 1 V to 5 V.

SUPPLY VOLTAGE REQUIREMENT

I_max = 20 mA unless an over-range current is stated; all series resistances are included.

MAXIMUM TOTAL LOOP RESISTANCE

R_L is wire plus receiver resistance in series; with V in volts and I in amperes, R is in ohms.

FLOW FROM DIFFERENTIAL PRESSURE

Head-type primary element, turbulent flow, constant fluid density; Q_max is the flow at full-scale differential pressure.

LOOP CURRENT FROM FLOW, NO SQUARE-ROOT EXTRACTOR

Same conditions as the flow law; with a square-root extractor the relation becomes linear, I = 4 + 16 Q/Q_max mA.

Where this was asked: 2024 (1). See the 1 previous-year question on 4-20 mA & networks. This shows what was asked, not what will be asked.