GATE 2022 EE Q.24: solution and answer

GATE 2022 · EEQ.24 · 1 mark · MCQ

The type of single-phase induction motor, expected to have the maximum power factor during steady state running condition, is

  1. (A)

    split phase (resistance start).

  2. (B)

    shaded pole.

  3. (C)

    capacitor start.

  4. (D)

    capacitor start, capacitor run.

See the question in the paper

Answer and solution

ANSWER

The single-phase induction motor type expected to have the maximum power factor during steady-state running is capacitor start, capacitor run.

Official answer: DSource: Official answer key, GATE 2022 EE (IIT Kharagpur)

  1. Running power factor of a single-phase induction motor is determined by whatever remains permanently in circuit in the auxiliary-winding path during steady-state running, not by the starting arrangement alone.

  2. Split-phase (resistance-start) motor: the auxiliary (starting) winding is disconnected by a centrifugal switch once the motor reaches about 75% of synchronous speed. During running, phase-splitting is provided only by the natural resistance/reactance unbalance of the main winding, so the running power factor is relatively poor.

  3. Shaded-pole motor: it has no auxiliary winding or capacitor circuit at all; a shading coil produces an auxiliary lagging flux only for starting torque. This construction is known for very low running power factor and low efficiency — the poorest of the four options.

  4. Capacitor-start motor: like the split-phase motor, its (large, electrolytic) capacitor and auxiliary winding are switched OUT of circuit after starting by a centrifugal switch. During steady running it therefore behaves essentially as a single-winding motor, with no permanent power-factor correction — its running power factor is not materially better than split-phase.

  5. Capacitor-start, capacitor-run motor: it uses two capacitors — a large starting capacitor that is disconnected after start, and a smaller running capacitor that stays permanently connected in series with the auxiliary winding during running.

  6. This permanently connected running capacitor is sized to bring the auxiliary-winding current close to quadrature (90°) with the main-winding current at rated running load, closely approximating balanced two-phase operation.

  7. Because balanced two-phase-like operation is the condition for near-unity/maximum power factor in such machines, the capacitor-start-capacitor-run motor has the best running power factor (and best running efficiency) among the four listed types.

KEY IDEA

Running power factor in a single-phase induction motor depends on what remains permanently connected in the auxiliary-winding circuit during steady running, not on the starting arrangement. Only a permanently connected running capacitor, sized to bring the auxiliary winding current close to quadrature with the main winding at rated load, improves the running power factor toward that of a balanced two-phase machine.

WATCH OUT FOR

Confusing "best starting torque/performance" with "best running power factor" — a capacitor-start motor has excellent starting torque but its capacitor is switched OUT after starting, so it gives no running power-factor benefit; only a permanently connected running capacitor (as in capacitor-start-capacitor-run) improves the running power factor.

From the GATE 2022 EE paper. Every question of this paper · Download the full paper · All 17 Induction machines questions, with notes